ETS Diagnostics ETS4_Diagnostics_E0111b 4/37ĥ 2.2 Checking if an address exists and locating the device Figure 4: Check whether individual address exists In order to check whether an individual address exists, enter the individual address in the field Individual address and press the Check Existence button. The ETS program continually checks which devices are in programming mode. 2.1 Devices in Programming Mode Figure 3: List all existing addresses in a line If the programming LED of one or several devices has been switched on, the corresponding individual address(es) appear(s) in the selection window under Device(s) in Programming mode. The diagnostics function Individual addresses is used to: check whether devices with a specific individual address exist in the installation Locate devices: Check whether the individual addresses in the project match those loaded in the bus couplers. Possible causes for bus devices not responding within a line can include: wire breakage on the bus line polarity reversal of the bus line at a device pre-programmed devices installed in the wrong line bus devices incorrectly configured and/or parameterised incorrectly programmed device faulty device ETS Diagnostics ETS4_Diagnostics_E0111b 3/37Ĥ Figure 2: Diagnostics/Test: Individual addresses 2 Diagnostics: Individual addresses. After establishing that a certain function cannot be executed, one should proceed step by step to locate the error, starting with the sending bus device (sensor) and finishing with the receiving device (actuator), in order to be able to correct the error.
faulty luminaries) or in the cabling of the installation. First of all, it is necessary to rule out the possibility that the error is located in the electrical power system (230/400 V) of the installation (e.g. During fault location, it is extremely advisable to work systematically.
KNX ETS 4 DOWNLOAD PC
As the diagnostics function of ETS requires direct bus access, the PC or notebook must be connected to the KNX installation via an interface/local interface (e.g. Detailed and up to date documentation of the installation is vital to be able to detect such types of errors. When doing so, it is important to describe problems that arise as precisely as possible. 2 Table of Contents 1 Diagnostics and fault location Diagnostics: Individual addresses Devices in Programming Mode Checking if an address exists and locating the device Listing all existing addresses in a line Diagnostics: Device Info, reading out devices Diagnostics: Bus monitoring and Group monitoring Starting and stopping a telegram recording Bus Monitoring Group monitoring Properties of individual telegrams Options for telegram recording General Recording Colouring Conditions Saving telegrams Opening telegrams from file Clearing the telegram list Replaying telegrams Group addresses: Read value Group addresses: Write value Diagnostics: Project Check Device Check Group Address Check Topology Check Product Information Check Diagnostics: Online Error Diagnostics Diagnostics: Online Installation Diagnostics Wizard Diagnostics: Tool Diagnostics.34 ETS Diagnostics ETS4_Diagnostics_E0111b 2/37ģ Figure 1: Diagnostics and fault location 1 Diagnostics and fault location If a KNX installation does not function optimally, errors shall be localized as quickly as possible and rectified.